September 1, 2026

Ten States Standards and AWWA Specs: What Water Owners Scope

By:
Dallas Bond

If a bid set cites Ten States and AWWA, I know the job scope is already boxed in. That usually means fixed design limits, named material standards, set test steps, and a paperwork trail that can delay acceptance if even one item is missing.

Here’s the article in plain English:

  • Ten States usually sets the design side of scope:
    • Water main size, pressure, dead-end flushing
    • Gravity sewer slope and velocity
    • Pump station backup capacity
    • Wet-well detention time and flood elevation rules
  • AWWA usually sets the build side of scope:
    • Pipe, fittings, valves, and hydrants
    • Linings, coatings, PVC, and HDPE requirements
    • Pressure testing and disinfection steps
    • Product data, certifications, and closeout records
  • Owners often turn those standards into hard bid language such as:
    • 6–8 in. minimum water main size
    • 20 psi minimum residual pressure
    • 2.5 ft/s flushing velocity at dead ends
    • 2.0 ft/s full-flow sewer velocity
    • 30 minutes or less wet-well detention time
    • 1.25–1.5x working pressure for hydrostatic testing
    • Two coliform-negative sample rounds before service
  • For hiring and planning, the article’s point is simple:
    • PMs need to read scopes and track submittals
    • Supers need to sequence install, test, and chlorination work
    • Estimators need to price pipe class, valves, coatings, and test work
    • QA/QC staff need to track certs, reports, and lab results

My takeaway: these standards do more than guide design. They shape cost, crew skills, review risk, testing, and final acceptance.

Area What owners usually scope from it
Ten States Design limits, pressure, size, slope, velocity, redundancy
AWWA Materials, joints, coatings, testing, disinfection, records

If I’m reading a municipal utility scope, this is the first filter I use to see what must be built, how it must be installed, and what proof the owner will ask for at the end.

Ten States Standards vs. AWWA Standards: Water & Wastewater Scope Breakdown

Ten States Standards vs. AWWA Standards: Water & Wastewater Scope Breakdown

AWWA Standards | Credibility & Longevity

How Ten States Standards Set Owner Design Criteria

Ten States Standards give owners a shared starting point for design criteria. That’s why the same limits keep showing up in utility scopes, basis-of-design reports, and front-end specs. The Great Lakes–Upper Mississippi River Board (GLUMRB) built the standards to set limiting values and make practice more uniform across jurisdictions[16]. Owners then carry those values into design manuals, basis-of-design reports, and front-end specs. For estimators and project managers, that translation matters. It helps teams price scope more accurately and spot approval risk before it turns into a problem.

You can see this most clearly in water distribution requirements.

Water System Criteria Owners Commonly Require

When owners draft water distribution scope, a small set of Ten States-derived numbers comes up again and again. Many owner standards say mains serving fire hydrants must be at least 6 in. in diameter. Some public distribution standards set 8 in. as the minimum for public mains, based on local fire-flow targets[4][6][10].

Pressure limits show up just as often. Scope language commonly calls for at least 20 psi residual pressure at all points under peak flow conditions. Normal operating pressure is often kept around 60–80 psi, with no point below 35 psi under normal conditions[4][11][12].

Dead-end mains are another spot where owners closely track Ten States language. Standards often state that dead-end mains should be minimized by looping wherever practical. If a dead end can’t be avoided, it usually has to end with a hydrant, flushing hydrant, or blowoff sized to reach at least 2.5 ft/s flushing velocity in the main[6][7][8]. On paper, that may look like a small note. In the field, it can mean more fittings, more appurtenances, and more review risk.

The same pattern carries over to wastewater work, but the controlling limits change. Instead of pressure and flushing, the focus shifts to slope, velocity, and redundancy.

Wastewater Criteria That Drive Scope and Constructability

Gravity sewer scope often starts with a minimum full-flow velocity of 2.0 ft/s using Manning's formula, with n = 0.013[2][9]. Owners turn that into minimum slope tables by pipe diameter. A common example is 0.40 ft/100 ft for 8-in. pipe and 0.22 ft/100 ft for 12-in. pipe. Front-end specs often add that sewer slopes must not drop below those values unless the engineer gives specific approval[9][14][15].

Pump station scope follows the same basic idea. Ten States redundancy rules require stations to handle peak hourly flow with the largest unit out of service. Owners usually restate that directly in equipment specs as a firm capacity requirement[5][13].

Wet-well sizing adds another hard limit. Owner policies often cap detention time at 30 minutes or less at average daily flow. Some standards also set a minimum wet-well diameter of 72 in. so the structure can be built with workable dimensions[1][9].

The table below shows how common Ten States criteria turn into the wording owners place in scopes.

Table: Ten States Criteria Mapped to Owner Scope Wording

Standard Clause Design Parameter Typical Owner Scope Wording
Minimum main diameter (fire protection) ≥ 6–8 in. diameter Water mains shall be a minimum of 8 inches in diameter. Mains serving fire hydrants shall not be less than 6 inches.
System pressure 20 psi minimum; 60–80 psi normal Maintain at least 20 psi residual pressure under peak flow conditions, including fire-flow. Normal operating pressure shall remain around 60–80 psi, with no point below 35 psi under normal conditions.
Dead-end and flushing Loop mains; 2.5 ft/s flushing velocity Dead-end mains shall be minimized by looping. Where unavoidable, terminate with a flushing hydrant sized to achieve 2.5 ft/s in the main.
Gravity sewer velocity ≥ 2.0 ft/s at full flow, n = 0.013 Gravity sewers shall be designed with slopes sufficient to maintain a velocity of 2.0 feet per second when flowing full.
Gravity sewer slope (8-in. pipe) 0.40 ft/100 ft minimum Sewer slopes shall not be less than those shown in the utility's design standards unless specifically approved in writing.
Pump station redundancy Peak hourly flow with largest unit out Pump stations must handle peak hourly flow with the largest unit out of service.
Wet-well detention time ≤ 30 minutes at average daily flow Provide wet-well volume sufficient to keep detention time at 30 minutes or less at average daily flow.
Flood protection Equipment above defined flood elevation All critical equipment and electrical controls must be elevated above the defined flood elevation.

How AWWA Standards Become Material, Equipment, and Construction Specs

If Ten States sets the design limits, AWWA sets the rules for materials and installation. Owners often put AWWA references straight into Division 33 – Utilities and project specs. They do that either by citing the standard number or by adding local requirements on top. That wording tells contractors what to price, what to submit, and what to install.

Pipe, Fittings, Valves, and Hydrants

For buried water mains, owner scopes often tie together AWWA C150, C151, C111, and C104. A common clause calls for ductile iron pipe that meets C151, with thickness designed under C150, cement-mortar lining under C104, and push-on or mechanical joints under C111. In one sentence, that sets the pipe class, joint type, lining, and submittal needs before buying starts.

Ductile iron pipe pressure class has a direct effect on wall thickness and cost. Many municipal guides use:

  • 350 psi for 3–12 in.
  • 250 psi for 14–20 in.
  • 200 psi for 24 in. and larger [18][26]

For fittings, owners usually split the spec by size and service demand. Compact ductile-iron fittings under C153 are common for smaller diameters. Standard-body ductile-iron fittings under C110 are more common for larger diameters or heavier-duty service. In most cases, fittings are expected to match the pipe lining and coating requirements.

Valves are usually scoped by valve type and pressure rating. Gate valves fall under C509/C515, butterfly valves under C504, check valves under C508, and hydrants under C502. Common working pressure ratings are 200 psi for 3–12 in. gate valves and 150 psi for 14–36 in. valves [22][23][24]. For hydrants, owners often ask for a dry-barrel unit with a 5-1/4-in. valve opening, three hose nozzles, one pumper nozzle, and a mechanical-joint shoe [3][18][20].

Coatings, Linings, and Non-Metallic Pipe

After the pipe and appurtenances are chosen, owners use AWWA standards to pin down corrosion protection and potable-water compliance. Linings and coatings affect corrosion, service life, and approval. Cement-mortar lining under C104 is the default choice for ductile iron distribution mains. For exterior protection in aggressive soils, owners may specify fusion-bonded epoxy under C550. In steel-pipe work, coating systems may point to C210 or C213. The corrosion setting drives that choice. Low-resistivity soils, high-chloride conditions, or marine exposure often lead owners to enhanced epoxy, polyolefin wraps, or cathodic protection.

Potable-water-contact materials should carry NSF/ANSI 61 certification. Owners usually push that requirement into the submittal package, so manufacturers have to show third-party certification for materials and linings that touch drinking water.

For non-metallic pipe, C900 is the main AWWA standard for PVC pressure pipe in the 4–12 in. range. Owners usually name the pressure class right in the spec, such as DR18 at 235 psi or DR14 at 305 psi. They may also call for blue pipe, integral bell elastomeric gasket joints, and NSF/ANSI 61 and 14 listings [17][19][21][25]. Where HDPE is allowed, C906 governs the pipe, and the scope language usually identifies the PE grade, SDR, and fusion method. Owners often add location-based limits too. A spec might allow PVC for mains 12 in. and smaller in residential streets, while requiring ductile iron under arterial roadways.

The table below condenses the AWWA standards owners most often turn into scope language.

Table: Major AWWA Standards and the Scope Items They Control

AWWA Standard Material / Component Pressure Class / Rating Joint Requirement Lining / Coating Common Owner Spec Wording
C150 / C151 Ductile iron pipe 150–350 psi; commonly 350 psi for 3–12 in., 250 psi for 14–20 in., and 200 psi for 24 in. and larger [18][26] Per C111 Cement-mortar per C104 Ductile iron pipe shall conform to AWWA C151, with thickness designed per AWWA C150, cement-mortar lined per C104, and joints per C111
C110 / C153 Ductile-iron fittings As specified by pipe/system rating Mechanical joint or flanged as specified Cement-mortar per C104; exterior coating per owner standard Compact fittings per C153 for smaller diameters; standard-body ductile-iron fittings per C110 for larger diameters
C111 Rubber-gasket joints - Push-on, mechanical, or restrained joints - Defines rubber-gasket joint type and assembly
C509 / C515 Resilient-seated gate valves Commonly 200 psi for 3–12 in. and 150 psi for 14–36 in. [22][23][24] Mechanical joint ends per C111 Often FBE inside and out per C550 Gate valves 2–12 in. resilient seated, 200 psi minimum working pressure, MJ ends
C504 Rubber-seated butterfly valves As specified by system Flanged or mechanical as specified As specified Butterfly valves on larger mains or plant piping
C508 Check valves As specified by pump system As specified As specified Check valves at pump discharge or well headers
C502 Dry-barrel fire hydrants - Mechanical joint shoe - Dry-barrel hydrants with 5-1/4-in. valve opening, 3 hose nozzles, 1 pumper nozzle [3][18][20]
C550 Fusion-bonded epoxy for ductile iron components - - Factory-applied FBE for ductile iron pipe and fittings FBE coating for aggressive-soil burial
C210 / C213 Steel water pipe coatings and linings - - Liquid epoxy or fusion-bonded epoxy, depending on standard and service Steel pipe coatings selected based on corrosion environment
C900 PVC pressure pipe DR18 = 235 psi; DR14 = 305 psi [17][19][21][25] Integral bell, elastomeric gasket NSF/ANSI 61 and 14 listed PVC pressure pipe 4–12 in., blue for potable water
C906 HDPE pressure pipe Based on SDR and PE designation Butt fusion or electrofusion NSF/ANSI 61 where potable HDPE pipe per C906, PE grade and SDR as specified

Owner Scope Items: Testing, Disinfection, Submittals, and Acceptance

After installation, owners don't accept the work until pressure testing, disinfection, and documentation all check out. If even one test fails, or one report is missing, the whole job can stall. Tie-ins, paving, and closeout often sit on hold until these last approval steps are cleared.

These are the final gates before a main can go into service.

Pressure Testing and Disinfection Requirements

For water mains, owners often tie pressure testing to AWWA C600 and Ten States Standards. In plain terms, the main has to prove it can hold pressure before anyone signs off.

Typical scope language calls for a test pressure of 1.25 to 1.5 times the working pressure. In many cases, that means not less than 150 psi at the lowest point of the test section. At the same time, the test pressure can't go above the design pressure of the pipe or thrust restraints. Most owners also want the test held for a continuous 2 hours, with pressure kept in a tight range, often ±5 psi. Leakage is then checked by measuring the makeup water required and comparing it to the owner's allowed limit.

Owners also tend to require:

  • Calibrated gauges
  • Advance notice before testing
  • Signed test forms before acceptance

Once the pressure test passes, disinfection comes next. Under AWWA C651, owners usually require high-velocity flushing first, often around 3.0 ft/s or higher, to clear out debris before chlorine is added.

The chlorine dose depends on the method used, and owners usually require a 24-hour contact period. If the schedule is tight, some owners allow the slug method at 100 mg/L for 3 hours, with a residual of at least 50 mg/L maintained through the slug period. After the contact time is met, the main is flushed, dechlorinated, and sampled.

Before the main can enter service, owners typically require two consecutive coliform-negative sample sets, taken 16 to 24 hours apart. Sample spacing is usually every 1,000 to 1,200 ft, plus the ends and branches. That may sound like a lot of sampling, but it makes sense. A clean test at one point in the line doesn't prove the whole main is ready.

Submittals, Certifications, and Compliance Records

Before construction starts, contractors have to submit product data, shop drawings, AWWA compliance affidavits, and NSF/ANSI 61 certifications for materials that touch potable water. Owners expect all of that to be accepted before installation begins.

After field work is done, there's a second round of paperwork. And this part matters just as much as the pipe in the ground.

Owners usually require hydrostatic test reports with time-stamped readings, leakage calculations, gauge calibration data, and pass/fail sign-off. They also want disinfection records that show chlorine dose, initial and final residuals, contact time, and the dechlorination method. On top of that, they require certified bacteriological lab results with sample locations, dates, and chain-of-custody details.

If submittals are missing or late at any point, owners often stop the next step cold. Testing, tie-ins, or service activation may not be approved until the paperwork is complete. There's also a clear rework risk: if installed materials can't be matched back to accepted submittals, owners may require removal and replacement even if the testing itself passed.

These records don't just document the job. They also make it clear which field roles need to be staffed for utility work.

Tables: Testing Requirements and Submittal Matrix

Standard Referenced Test / Procedure Typical Criteria Documentation Required
AWWA C600 Pressure test 1.25 to 1.5× working pressure, commonly ≥150 psi at the lowest point Pressure test report with time-stamped readings and gauge calibration data
AWWA C600 Test duration Continuous 2 hours, pressure held within ±5 psi Time log with start/end pressures and makeup water required
AWWA C600 Allowable leakage Per AWWA formula or no measurable leakage Leakage worksheet and signed test form
AWWA C651 Pre-chlorination flush About 3.0 ft/s; three pipe volumes Flushing log with velocity and volume confirmation
AWWA C651 Chlorination – continuous feed / tablet 25 mg/L initial dose; 24-hour contact; residual ≥10 mg/L (continuous) or ≥0.2 mg/L (tablet) Chlorine dose calculation, initial and final residual readings
AWWA C651 Chlorination – slug method 100 mg/L for 3 hours; residual ≥50 mg/L throughout slug Slug chlorination log with residual readings at intervals
AWWA C651 Dechlorination Neutralize to regulatory limit before discharge Dechlorination method, discharge location, and confirmation readings
AWWA C651 Bacteriological acceptance Two consecutive coliform-negative sample sets, 16–24 hrs apart; samples spaced every 1,000–1,200 ft plus ends and branches Certified lab reports with sample locations, dates, and chain-of-custody
Scope Item Required Document AWWA / Ten States Reference
Ductile iron pipe Product data, affidavit of AWWA compliance AWWA C151
Fittings Shop drawings, affidavit of compliance AWWA C110 / C153
Valves and hydrants Shop drawings, product data AWWA C509 / C515 / C504 / C502
Coatings and linings Coating certification, NSF/ANSI 61 documentation Applicable AWWA and Ten States requirements
Pressure test Pressure test report, leakage calculations, gauge calibration AWWA C600
Disinfection Chlorination log, dechlorination plan, residual readings AWWA C651
Bacteriological acceptance Certified lab results, chain-of-custody forms AWWA C651
Closeout As-builts, O&M manuals, compliance records Ten States Standards

That checklist drives the technical skills owners need on site.

What These Standards Mean for Hiring, Planning, and Risk Control

When a scope cites Ten States and AWWA, staffing, sequencing, and closeout are driven by those standards. If you know that before mobilization, you can avoid rework, failed tests, and change-order fights. That’s why role-specific standards knowledge should be the first screen in hiring.

Technical Skills That Matter by Role

Each role needs a different level of standards knowledge. A project manager who can’t read utility specs may miss exclusions or misalign subcontractors. A superintendent who doesn’t grasp pressure testing sequence can leave a gap between testing and disinfection. An estimator who isn’t familiar with AWWA requirements can underprice pipe classes, valves, coatings, restrained joints, and testing.

Different utility roles need different depth. Here’s where that shows up most.

Role Required Preferred Trainable
Project Manager Read utility specs; manage submittals and RFIs Prior municipal water/wastewater project experience Owner-specific standard details and forms
Superintendent Installation sequencing; testing and disinfection coordination Pressure testing and chlorination experience Local inspector hold points and punch-list procedures
Estimator Plan/spec interpretation; quantity takeoff Familiarity with AWWA material standards and approved products Owner-specific pricing conventions
Field Engineer Track as-builts, tests, and inspection records Experience with utility inspectors and compliance documentation Project-specific closeout package formats
QA/QC Lead Verify materials, certifications, and test results AWWA/Ten States compliance requirements Owner-specific submittal tracking systems

A strong candidate in any of these roles should be able to talk through specific scope items like pipe class selection, valve spacing, allowable leakage criteria, and chlorination methods, not just say they’ve done “utility work.” That kind of detail is one of the clearest signs of actual field exposure.

Those differences should shape how utility candidates are screened.

How iRecruit.co Builds Stronger Candidate Profiles for Utility Work

Utility hiring works better when candidate profiles show owner-spec experience, not just years on site. When iRecruit.co builds profiles for water and wastewater projects, the focus stays on owner-spec-driven work: the project types completed, the owner types served, the standards involved, and the exact technical duties handled.

For a municipal water main project, a strong profile should show ductile iron pipe experience, valve and hydrant work, service connections, pressure testing, and disinfection. For a wastewater collection project, it should show gravity sewer installation, manhole construction, infiltration/exfiltration control, and bypass pumping under public-agency specs. For a pump station, it should include mechanical and electrical coordination, equipment submittals, startup, and acceptance testing.

Candidates who have worked with municipal inspectors, managed submittal packages, or led QA/QC closeout tend to be strong fits. That’s often where Ten States and AWWA requirements create the most friction.

The same standards that define the scope also shape who can get the job through acceptance.

Conclusion: Standards-First Scoping Cuts Project and Hiring Risk

Standards-first scopes lower risk because they define the work, the skill needs, and the closeout requirements at the start. The payoff is practical: fewer rejected submittals, failed tests, RFIs, and scope-gap change orders. On the staffing side, it helps teams figure out early whether a job needs municipal utility experience, QA/QC depth, commissioning, or compliance-documentation skills before the wrong hire causes trouble in the field.

Standards literacy isn’t just a technical credential. It’s also a project control tool and a hiring filter.

FAQs

How do Ten States and AWWA differ?

Ten States Standards and AWWA specifications serve different purposes in utility project scoping.

Ten States Standards lay out broad design and public health criteria that state agencies use to support safe, reliable water systems. They set the baseline for how a system should be planned.

AWWA specifications, by contrast, get into the technical details. They cover material and performance standards for items like pipe, valves, and testing methods.

Put simply, Ten States Standards set the baseline, while AWWA specifications spell out the products and methods used to meet it.

Which standard affects project cost more?

Neither. Cost impact depends more on how clearly the scope spells out Ten States Standards and AWWA requirements, and how strictly those requirements are applied during design and procurement.

When the scope is vague, contractors may add 10% to 20% contingency to cover uncertainty. Owners can control costs by using these standards to set clear requirements, support steady estimates, and line up technical needs with budget limits.

What documents usually delay final acceptance?

Final acceptance often gets pushed back when key turnover documents for facility operations are missing or half-finished. The usual trouble spots are:

  • as-built drawings
  • test results
  • warranties
  • final O&M manuals

Delays can also happen when occupancy approvals aren't in place or punch list items are still open. Until those contract and legal requirements are fully wrapped up, owners will usually hold back final payment or retainage.

Related Blog Posts

Keywords:
Ten States Standards, AWWA, water main specs, pressure testing, disinfection, ductile iron pipe, submittals, QA/QC
Free Download

Data Center Construction Labor Trends in 2026

Thank you! Your submission has been received!
Oops! Something went wrong while submitting the form.

More mission critical construction news

Intel Ohio One: Construction Status and the Workforce Behind the New Albany Campus
September 1, 2026

Intel Ohio One: Construction Status and the Workforce Behind the New Albany Campus

New Albany site moves from underground to vertical construction; hiring shifts from earthwork to MEP, commissioning and tool-install specialists.
TSMC Arizona Fab Expansion: What the Third Fab Means for Construction Hiring
September 1, 2026

TSMC Arizona Fab Expansion: What the Third Fab Means for Construction Hiring

Third Arizona fab tightens construction labor, raises pay, and ups schedule risk; hire MEP, commissioning, and project leaders early.
EPCM vs EPC on Mine Builds: What Owners Choose and Why
September 1, 2026

EPCM vs EPC on Mine Builds: What Owners Choose and Why

EPC gives price and schedule certainty; EPCM gives owners control and flexibility but needs larger owner teams and assumes more risk.
UFC for Contractors: Unified Facilities Criteria Explained
September 1, 2026

UFC for Contractors: Unified Facilities Criteria Explained

Treat UFC as contract scope: identify governing UFCs early to avoid antiterrorism, QC, and commissioning surprises on DoD projects.